AIO288/1 Bachmann Analog Input/Output Module

Stok Kodu: AIO288/1

Teknik özellikler

  • Manufacturer: Bachmann

  • Condition:New with Original Package

  • Product Type: Analog Input/Output Modules

  • Country of Origin: Austria

  • Payment:T/T, Western Union

  • Shipping port: Xiamen

  • Warranty: 12 months

Bu ürünü talep ederek, Hizmet Şartlarını incelediğinizi ve kabul ettiğinizi onaylamış olursunuz. Lütfen tüm işlemlerin çevrimdışı olarak işleneceğini unutmayın.

%100 Orijinal ve Otantik
% 100 Yepyeni, gönderilmeye hazır
Destek İadesi, 7X24h Hizmet
Tüm Ürünlerde 1 Yıl Garanti

Daha fazla kişiye ulaşmamıza yardımcı olun! Bu ürünü ağınızla paylaşın ve desteğinizi gösterin!

Product Description

The Bachmann AIO288/1 is an analog input/output module for acquiring voltage, current, and temperature signals and generating analog voltage outputs. It supports voltage inputs of +/-1 V or +/-10 V, current inputs from 0 mA to 20 mA, and selectable Pt100 or Pt1000 temperature sensors. The module provides up to 8 voltage input channels, 8 voltage output channels, 8 current input channels, and 4 temperature input channels, with 14-bit resolution for the specified signal types.

Hardware Specifications

Parameter Specification
Model AIO288/1
Brand Bachmann
Product Type Analog Input/Output Module
Voltage Input Channels Max. 8
Voltage Input Range +/-1 V or +/-10 V
Voltage Input Impedance > 100 kOhm
Voltage Input Resolution 14 bit
Permitted Common-Mode Voltage Max. +/-1 V
Voltage Input Accuracy at 25 deg C Max. +/-0.05% of input voltage range
Voltage Input Cutoff Frequency 1.5 kHz (3 dB)
Voltage Input Common-Mode Rejection > 60 dB
Voltage Input Sampling Time 200 us
Voltage Output Channels Max. 8
Voltage Output Range +/-10 V
Voltage Output Resolution 14 bit
Voltage Output Accuracy at 25 deg C Max. +/-0.025% of measuring range
Voltage Output Settling Time Max. 400 us to 1% of the output current range
Voltage Output Common-Mode Rejection > 60 dB
Voltage Output Refresh Cycle 200 us
Current Input Channels Max. 8
Current Input Range 0 mA to 20 mA
Current Input Impedance 243 Ohm
Current Input Resolution 14 bit
Maximum Current Input 35 mA (destruction limit)
Current Input Accuracy at 25 deg C Max. +/-0.1% of measuring range at 20 mA
Current Input Cutoff Frequency 1.5 kHz (3 dB)
Current Input Sampling Time 200 us
Temperature Sensor Types Pt100 or Pt1000, selectable
Temperature Input Channels Max. 4
Temperature Sensor Connection 2-wire or 4-wire
Temperature Range -100 deg C to +500 deg C
Temperature Input Impedance > 100 kOhm
Temperature Input Accuracy at 25 deg C Max. +/-0.1% of measuring range (600 K)
Temperature Input Cutoff Frequency 1.5 kHz (3 dB)
Temperature Resolution (LSB) 0.1 K
Temperature Sampling Time 200 us
Estimated Shipping Dimensions 5.4 x 5.2 x 11.8 cm
Weight 0.2 kg

Analog Signal Acquisition and Output

The voltage input channels measure signals within the selected +/-1 V or +/-10 V range. Their input impedance exceeds 100 kOhm, while the 14-bit resolution determines the digital granularity of the converted measurement. The 1.5 kHz cutoff frequency defines the specified input bandwidth at the 3 dB point.

The current input channels accept signals from 0 mA to 20 mA and use a 243 Ohm input impedance. The 35 mA maximum input current is a destruction limit, not a normal operating range. Therefore, keep the applied current within the specified measurement range during normal operation.

The voltage outputs generate signals from -10 V to +10 V. Their specified accuracy is +/-0.025% of the measuring range at 25 deg C. The stated maximum settling time is 400 us to 1% of the output current range; the original specification uses current-range terminology for a voltage output, so this condition requires confirmation before it serves as an output-response acceptance criterion.

Temperature Measurement

The temperature inputs support selectable Pt100 and Pt1000 resistance temperature detectors (RTDs), with 2-wire or 4-wire connections. The module covers a stated temperature range of -100 deg C to +500 deg C, with an accuracy of up to +/-0.1% of a 600 K measuring range at 25 deg C.

A 4-wire RTD connection can reduce the effect of lead resistance on resistance measurement. A 2-wire connection uses a simpler wiring arrangement, but lead resistance can contribute to measurement error. Confirm the selected sensor type and connection method against the system configuration before commissioning.

Frequently Asked Questions

Q: How many analog channels does the AIO288/1 support?

A: The supplied specifications list up to 8 voltage inputs, 8 voltage outputs, 8 current inputs, and 4 temperature inputs. These are the stated maximum counts for each signal type; confirm the intended configuration before assigning channels.

Q: Which temperature sensors can the AIO288/1 measure?

A: It supports selectable Pt100 and Pt1000 RTDs. The specified temperature range is -100 deg C to +500 deg C, with either 2-wire or 4-wire sensor connections.

Q: What does the 35 mA current limit mean?

A: The 35 mA value is identified as the destruction limit, not the normal measurement range. The specified current input range is 0 mA to 20 mA, so signals should remain within that range during normal operation.

Other Attributes

  • Country of Origin:  Austria
  • Lead Time: In Stock, 2 Working Days

 

In Stock Hot Items of Bachmann

WT205V AIO288 FM211
BS208 PCC200 DIO248
GIO212 CM202 BS206
MX220 ACR222/2 DIO216
MPC240/W ISI222 PTAI216
NT250 MPC270 MPC240
SWI205 AI204/2 00016586-00


Our Competitive Brands

  • - ABB Advant-800xA,Advant OCS,Bailey Infi 90 and Net 90,H&B Freelance 2000,DSQC Robots,IGCT / IGBT
  • - GE General Electric Field Control, Genius I/O, QuickPanel, RX3i PacSystem, Series 90, Series 90, Series VersaMax
  • - Allen Bradley Allen-Bradley SLC500, MicroLogix, CompactLogix, ControlLogix, PLC-5, Panel View,
  • - Bently Nevada 3300 System, 3500 System
  • - Honeywell 7800 Series, FSC, IPC, Mxopen, TDC 2000, TDC 3000, Experion PKS(C200,C300)
  • - Yokogawa Centum CS - Centum VP, Centum XL - micro XL, FA-M3, ProSafe-PLC
  • - Ovation, Foxboro, EPRO, Emerson DeltaV, Fuji, Siemens, HIMA, Prosoft, Invensys Triconex, ICS TRIPLEX, Woodward, Bachmann, Schneider

 

TEL: +86 18030205725     E-MAIL: manskiwong@cambia.cn

Question 1: Is Our Price Competitive?

NEW-GEN collaborates with over 50 countries worldwide. As a leading supplier in China, we can provide significant discounts to customers based on market demand.

Question 2: What Is The Warranty Period?

We offer a standard one-year warranty for all new and original items.

Question 3: What Payment Methods Do We Accept?

We accept 100% T/T (Telegraphic Transfer) before shipping. For items with a lead time, a 30% deposit is required in advance, with the remaining 70% balance due before shipping. If you have an agent in China, please contact us for RMB transfer.

Question 4: What Shipping Methods Do We Use?

We primarily utilize carriers such as FedEx, DHL, UPS, BRE, etc. If you have an account with any of these carriers, you can arrange the shipping yourself. Additionally, we offer free shipping to China freight forwarders.

Question 5: What Is Our Delivery Time?

Typically, delivery takes around 1-3 days after receiving the advance payment. For items with a quoted lead time, delivery will occur as per the specified lead time.

Question 6: How Do We Package The Goods?

Our packaging process involves multiple layers of protection. Initially, the product is placed in its original box, sealed with a label. Then, we add a layer of bubble wrap to safeguard against collisions during transportation. Finally, all products are securely packed in sturdy boxes for further protection.

Question 7: How Can Customers Contact Us And Request A Quote?

Customers can inquire via email, WhatsApp, WeChat, Skype, or any preferred communication platform. Simply reach out to us, and we'll promptly provide a quote tailored to your needs.