Pepperl+Fuchs KFD0-HMS-16(3415024) HART Multiplexer Slave Module
Техничке спецификације
Manufacturer: PEPPERL+FUCHS
Condition:New with Original Package
Product Type: HART Multiplexer Slave Modules
-
Country of Origin: Germany
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Подношењем захтева за ову ставку потврђујете да сте прегледали и прихватили наше Услове и одредбе . Имајте на уму да ће све трансакције бити обрађене ван мреже.
Питајте стручњака
Помозите нам да допремо до више људи! <стронг>Делите овај производ стронг>са својом мрежом и <стронг>покажите подршку!стронг>
Product Description
Configured for HART signal channel interfacing in the K-System HART multiplexer network, the Pepperl+Fuchs KFD0-HMS-16(3415024) (KFD0-HMS-16 HART multiplexer slave module) provides direct physical and electrical execution. The module connects to a KFD2-HMM-16 master through a 14-channel flat cable and handles 16 nonintrinsically safe HART field device signal channels supporting HART revisions 5 to 7.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | KFD0-HMS-16(3415024) |
| Base Model | KFD0-HMS-16 |
| Brand | Pepperl+Fuchs |
| Product Type | HART Multiplexer Slave Modules |
| Series | K-System |
| Function | 16-channel HART signal channel slave interface |
| Master Connection | KFD2-HMM-16 HART Multiplexer Master |
| HART Signal Channels | 16 channels |
| Signal Type | Nonintrinsically safe HART field device input |
| Supported HART Revisions | Revision 5 to 7 |
| External Power Requirement | No external power required |
| Analog Connection | 26-pin flat cable |
| Master-Slave Connection | 14-pin flat cable |
| Leakage Current | Less than 3 uA at -20 to 85 deg C |
| External Terminating Resistor | 230 to 500 ohm standard; up to 1000 ohm possible |
| Output Voltage | At least 400 mV peak-to-peak with specified terminating resistance |
| Output Resistance | 100 ohm or lower, capacitive coupling |
| Input Impedance | According to HART specification |
| Input Voltage Range | 0.08 to 4 V peak-to-peak; typical +/- 5.2 V local reference |
| EMC Standard | EN 61326-1:2006 |
| EMC Directive | 2004/108/EC |
| Degree of Protection | IP20 |
| Origin | Not specified in the provided data |
| Weight | Approx. 100 g |
| Dimensions | 20 x 93 x 115 mm |
| Housing Type | B1 |
| Operating Temp | -20 to 60 deg C |
| Storage/Extended Temperature Data | Leakage current specified from -20 to 85 deg C |
| Power Consumption | No external power required |
| Mounting | 35 mm DIN mounting rail according to EN 60715:2001 |
| Ex Classification | II 3G Ex nA II T4 X |
| Functional Safety | Up to SIL3 according to IEC 61508 |
DIN-Rail Signal Interface Characteristics
The KFD0-HMS-16(3415024) uses a DIN-rail-mounted housing and connects directly with the KFD2-HMM-16 through the specified 14-pin master-slave flat cable. Therefore, the installation does not require a separate external power supply for the slave module.
The module transfers HART communication signals from 16 field device channels through the analog connection interface. Capacitive output coupling and an output resistance of 100 ohm or lower define the electrical connection behavior.
Although this model processes nonintrinsically safe HART channels, the provided application documentation also identifies requirements for installation associated with Ex-area applications. Consequently, the applicable Pepperl+Fuchs statements and declarations of conformity must govern the final installation.
Frequently Asked Questions
Q: Does the KFD0-HMS-16(3415024) require an external power supply?
A: No. The provided specification states that the module requires no external power supply. It operates in connection with the KFD2-HMM-16 HART Multiplexer Master.
Q: Which HART field devices can connect to this module?
A: The module accepts nonintrinsically safe HART field device signals and supports HART protocol revisions 5 through 7.
Q: What terminating resistance should be used for the HART output connection?
A: The standard external terminating resistance range is 230 to 500 ohm. The specification permits values up to 1000 ohm where the application allows this configuration.
Field Installation Guidelines
Mount the KFD0-HMS-16(3415024) on a 35 mm DIN rail installed according to EN 60715:2001. Maintain adequate cabinet spacing for wiring access and heat dissipation within the specified ambient temperature range.
Connect the analog signal interface through the specified 26-pin flat cable. Then connect the KFD2-HMM-16 master and KFD0-HMS-16 slave interface using the specified 14-pin flat cable. Do not substitute cable pin assignments without verifying the applicable Pepperl+Fuchs documentation.
Route HART signal wiring separately from high-current switching conductors, motor cables, and other electrical noise sources. Where shielded field wiring is used, apply the shielding arrangement according to the plant grounding design and the applicable HART installation requirements.
Install the external terminating resistor within the specified electrical range and verify the resulting HART signal level during commissioning. In addition, observe the applicable Statement of Conformity, Declaration of Conformity, Attestation of Conformity, and installation instructions when the assembly is associated with Ex-area applications.
Other Attributes
- Country of Origin: Germany
Lead Time: In Stock, 2 Working Days
Our Competitive Brands
- - ABB Advant-800xA,Advant OCS,Bailey Infi 90 and Net 90,H&B Freelance 2000,DSQC Robots,IGCT / IGBT
- - GE General Electric Field Control, Genius I/O, QuickPanel, RX3i PacSystem, Series 90, Series 90, Series VersaMax
- - Allen Bradley Allen-Bradley SLC500, MicroLogix, CompactLogix, ControlLogix, PLC-5, Panel View,
- - Bently Nevada 3300 System, 3500 System
- - Honeywell 7800 Series, FSC, IPC, Mxopen, TDC 2000, TDC 3000, Experion PKS(C200,C300)
- - Yokogawa Centum CS - Centum VP, Centum XL - micro XL, FA-M3, ProSafe-PLC
- - Ovation, Foxboro, EPRO, Emerson DeltaV, Fuji, Siemens, HIMA, Prosoft, Invensys Triconex, ICS TRIPLEX, Woodward, Bachmann, Schneider
Question 1: Is Our Price Competitive?
NEW-GEN collaborates with over 50 countries worldwide. As a leading supplier in China, we can provide significant discounts to customers based on market demand.
Question 2: What Is The Warranty Period?
We offer a standard one-year warranty for all new and original items.
Question 3: What Payment Methods Do We Accept?
We accept 100% T/T (Telegraphic Transfer) before shipping. For items with a lead time, a 30% deposit is required in advance, with the remaining 70% balance due before shipping. If you have an agent in China, please contact us for RMB transfer.
Question 4: What Shipping Methods Do We Use?
We primarily utilize carriers such as FedEx, DHL, UPS, BRE, etc. If you have an account with any of these carriers, you can arrange the shipping yourself. Additionally, we offer free shipping to China freight forwarders.
Question 5: What Is Our Delivery Time?
Typically, delivery takes around 1-3 days after receiving the advance payment. For items with a quoted lead time, delivery will occur as per the specified lead time.
Question 6: How Do We Package The Goods?
Our packaging process involves multiple layers of protection. Initially, the product is placed in its original box, sealed with a label. Then, we add a layer of bubble wrap to safeguard against collisions during transportation. Finally, all products are securely packed in sturdy boxes for further protection.
Question 7: How Can Customers Contact Us And Request A Quote?
Customers can inquire via email, WhatsApp, WeChat, Skype, or any preferred communication platform. Simply reach out to us, and we'll promptly provide a quote tailored to your needs.