Bently Nevada 3500/33 16-Channel Relay Module
Tehniskās specifikācijas
Manufacturer: Bently Nevada
Condition:New with Original Package
Product Type: Relay Output Modules
-
Country of Origin: USA
Payment:T/T, Western Union
Shipping port: Xiamen
Warranty: 12 months
Iesniedzot pieprasījumu par šo preci, jūs apstiprināt, ka esat izskatījis un pieņēmis mūsu Noteikumus un nosacījumus. Lūdzu, ņemiet vērā, ka visas transakcijas tiks apstrādātas bezsaistē.
Jautājiet ekspertam
Palīdziet mums sasniegt vairāk cilvēku! Kopīgojiet šo produktu ar savu tīklu un izrādiet savu atbalstu!
Product Description
Bently Nevada 3500/33 16-Channel Relay Module
Configured for relay output execution in the Bently Nevada 3500 Machinery Protection System, the Bently Nevada 3500/33 (149986-01 + 149992-01) provides direct electrical switching through 16 independent SPDT relay channels. The 3500/33 uses the 149986-01 front module with the 149992-01 rear I/O module to execute programmed alarm, trip, and voting logic.
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 3500/33 |
| Part Numbers | 149986-01 + 149992-01 |
| Brand | Bently Nevada |
| Product Type | 16-Channel Relay Modules |
| System | 3500 Machinery Protection System |
| Front Module | 149986-01 Spare 16-Channel Relay Control Module |
| Rear I/O Module | 149992-01 Spare 16-Channel Relay Output Module |
| Relay Type | SPDT, epoxy-sealed relays |
| Channel Capacity | 16 independent relay channels |
| Channel Groups | 4 groups of 4 channels |
| Relay Operating Mode | Switch-selectable Normally De-energized (ND) or Normally Energized (NE) |
| Maximum Switched Voltage | 125 VDC / 250 VAC |
| Maximum Switched Current | 5 A |
| Maximum Switched Power | 70 W at 24 VDC; 1200 VA at 250 VAC |
| Minimum Switched Current | 100 mA at 5 VDC |
| Main Module Dimensions | 241 mm x 24.4 mm x 242 mm |
| Main Module Weight | 0.7 kg |
| I/O Module Dimensions | 241 mm x 24.4 mm x 99.1 mm |
| I/O Module Weight | 0.4 kg |
| Rack Space | 1 full-height front slot + 1 full-height rear slot |
| Indicators | OK LED, TX/RX LED, channel alarm LEDs |
| Rack Configuration Software | Version 3.3 or later |
| Data Acquisition Software | Version 2.40 or later |
| Origin | Not specified in supplied data |
Machinery Protection Relay Logic and Electrical Switching
The 3500/33 operates at the relay interface between the 3500 monitoring system and external alarm or shutdown circuits. The 149986-01 control module manages relay logic, while the 149992-01 rear module provides the corresponding field wiring interface.
Each of the 16 channels uses an SPDT relay. The channels operate in four groups of four, and each group can use Normally De-energized (ND) or Normally Energized (NE) operation through hardware selection.
The relay contacts switch external circuits according to configured alarm and voting logic. Therefore, field wiring must remain within the specified voltage, current, and switching-power limits.
The module also provides OK, TX/RX, and channel alarm indicators for local status and diagnostic observation. The TX/RX indicator corresponds to rack communication activity rather than a field relay contact signal.
For mechanical monitoring applications, the relay outputs can interface with protection circuits associated with rotor vibration, shaft position, speed, or other monitored machine conditions. However, the supplied specifications do not define the individual alarm logic assigned to each channel.
Frequently Asked Questions
Q: Does the 3500/33 provide 16 relay channels through one front module?
A: The complete assembly uses the 149986-01 front relay control module together with the 149992-01 rear relay output module. Together, they provide 16 relay channels.
Q: What relay contact limits apply to the 3500/33?
A: The specified limits are 125 VDC or 250 VAC maximum switched voltage, 5 A maximum switched current, 70 W at 24 VDC, and 1200 VA at 250 VAC. The minimum switched current is 100 mA at 5 VDC.
Q: Which software versions support this relay module?
A: The supplied data specifies 3500 Rack Configuration Software version 3.3 or later and 3500 Data Acquisition Software version 2.40 or later.
Field Installation Guidelines
- Install the 149986-01 front module in the designated full-height front slot of the 3500 rack.
- Install the 149992-01 rear I/O module in the corresponding full-height rear position.
- Verify that the relay contact load remains within the specified voltage, current, and power limits.
- Configure each relay group according to the required Normally De-energized (ND) or Normally Energized (NE) operating mode.
- Route relay wiring separately from low-level vibration and measurement signal wiring where practical.
- Maintain appropriate physical separation between relay circuits and sensitive monitoring signals to reduce electrical coupling.
- Connect field wiring according to the applicable 3500 rack wiring documentation and site electrical standards.
- Verify relay contact state and channel indication during commissioning before connecting the outputs to final alarm or shutdown circuits.
- Confirm rack communication through the TX/RX indication and check the OK status before placing the protection circuit into service.
- Use the specified software versions or later versions identified in the supplied technical data.
Other Attributes
- Series: 24765 and 135613 Case Expansion Transducer Systems
- Country of Origin: USA
- Lead Time: In Stock, 2 Working Days
In Stock Hot Items of The Bently Nevada
Our Competitive Brands
- - ABB Advant-800xA,Advant OCS,Bailey Infi 90 and Net 90,H&B Freelance 2000,DSQC Robots,IGCT / IGBT
- - GE General Electric Field Control, Genius I/O, QuickPanel, RX3i PacSystem, Series 90, Series 90, Series VersaMax
- - Allen Bradley Allen-Bradley SLC500, MicroLogix, CompactLogix, ControlLogix, PLC-5, Panel View,
- - Bently Nevada 3300 System, 3500 System
- - Honeywell 7800 Series, FSC, IPC, Mxopen, TDC 2000, TDC 3000, Experion PKS(C200,C300)
- - Yokogawa Centum CS - Centum VP, Centum XL - micro XL, FA-M3, ProSafe-PLC
- - Ovation, Foxboro, EPRO, Emerson DeltaV, Fuji, Siemens, HIMA, Prosoft, Invensys Triconex, ICS TRIPLEX, Woodward, Bachmann, Schneider
TEL: +86 18030205725 E-MAIL: manskiwong@cambia.cn
Question 1: Is Our Price Competitive?
NEW-GEN collaborates with over 50 countries worldwide. As a leading supplier in China, we can provide significant discounts to customers based on market demand.
Question 2: What Is The Warranty Period?
We offer a standard one-year warranty for all new and original items.
Question 3: What Payment Methods Do We Accept?
We accept 100% T/T (Telegraphic Transfer) before shipping. For items with a lead time, a 30% deposit is required in advance, with the remaining 70% balance due before shipping. If you have an agent in China, please contact us for RMB transfer.
Question 4: What Shipping Methods Do We Use?
We primarily utilize carriers such as FedEx, DHL, UPS, BRE, etc. If you have an account with any of these carriers, you can arrange the shipping yourself. Additionally, we offer free shipping to China freight forwarders.
Question 5: What Is Our Delivery Time?
Typically, delivery takes around 1-3 days after receiving the advance payment. For items with a quoted lead time, delivery will occur as per the specified lead time.
Question 6: How Do We Package The Goods?
Our packaging process involves multiple layers of protection. Initially, the product is placed in its original box, sealed with a label. Then, we add a layer of bubble wrap to safeguard against collisions during transportation. Finally, all products are securely packed in sturdy boxes for further protection.
Question 7: How Can Customers Contact Us And Request A Quote?
Customers can inquire via email, WhatsApp, WeChat, Skype, or any preferred communication platform. Simply reach out to us, and we'll promptly provide a quote tailored to your needs.